It is 8 gauge wire. Rated for up to 40 amps.
Our community has rated this post as helpful. If you agree, why not thank mkzmkz
Our community has rated this post as helpful. If you agree, why not thank Masejoer
Sign up for a Slickdeals account to remove this ad.
Electric Stove
Electric Clothes Dryer
Central Heat With Electric Coils
Tankless or Tank Water Heater
Larger Central Air Condensers
Any of these will be plainly marked with amperage requirements for circuit sizing, which easily translates to wire and breaker size. All of the above typically have a dedicated circuit and breaker.
Our community has rated this post as helpful. If you agree, why not thank SilentAgnostic
Refer to the Ampacity charts: https://www.cerrowire.c
Useful for solar if you want to run low voltage/high amperage.
Lot of people run high voltage to save on copper.
Sign up for a Slickdeals account to remove this ad.
Our community has rated this post as helpful. If you agree, why not thank dherman
Refer to the Ampacity charts: https://www.cerrowire.c
Second, that wire is only good for 65A noncontinuous loads at 75c. If you want 60A continuous as you would need for an EV, you'd need something rated for 75A, or 4AWG THHN. Your wire is undersized.