WOLFBOX AUTO via Amazon has
WOLFBOX 50 Amp J1772 Level 2 Indoor/Outdoor Smart EV Charger w/ NEMA 14-50 Plug & 25ft Cable (WE50) on sale for $429.99 - $172 with promo code
40WOLFBOX at checkout =
$257.99.
Shipping is free.
Thanks to Deal Editor
iconian for sharing this deal.
- Note: You must be logged in to clip coupons or apply promo codes. Coupons/Promo codes are typically single-use, may vary by account or may need to be re-applied in order to discount properly.
Details:
- 50A Level 2 EV charger: up to 48 miles per charging hour (requires 70A+ circuit breaker); 40A delivers 38 miles/hour
- Flexible operation: app control, RFID card, or plug-and-charge
- CSA & FCC certified, UL2594 compliant with 8 safety protections (leakage, over-current, short circuit, etc.)
- NEMA 4X waterproof and dustproof housing
- Smart app: schedule up to 4 charging groups, adjust amperage, track costs, and charge during off-peak hours
- Adjustable amperage via dial to prevent overload; internal temperature monitoring and 950°C flame-retardant design
- 25-foot charging cable for flexible reach
- Compatible with all J1772 EVs (Tesla requires NACS adapter)
- 24/7 customer support with lifetime assistance
Top Comments
The issue is that the National Electrical Code (NEC) requires that a continuous load should not exceed 80% of the rating of electrical equipment. This means that a NEMA 14-50 receptacle with a 50A breaker and 8GA THHN is fine for a 50A intermittent load like a welder but is only is good for a continuous load of 40A. The NEC defines a continuous load as any electrical draw expected to run continuously for 3 hours or longer. Examples include EV chargers, pool pumps, and electric space heaters.
Join The Conversation
Share your experience with the Slickdeals community
Share information with the community. Please follow our Community Guidelines and be kind!
51 Comments
Sign up for a Slickdeals account to remove this ad.
edit: Looks like only the hard-wired version is on sale. Coupon doesn't work on NEMA 14-50 version.
OP, could you either modify the title or add to the description?
Our community has rated this post as helpful. If you agree, why not thank FuschiaHome408
The issue is that the National Electrical Code (NEC) requires that a continuous load should not exceed 80% of the rating of electrical equipment. This means that a NEMA 14-50 receptacle with a 50A breaker and 8GA THHN is fine for a 50A intermittent load like a welder but is only is good for a continuous load of 40A. The NEC defines a continuous load as any electrical draw expected to run continuously for 3 hours or longer. Examples include EV chargers, pool pumps, and electric space heaters.
As for the EV rating, I know the receptacle can be EV rated, I wasn't aware that the plug can be EV-rated as well, huh
Sign up for a Slickdeals account to remove this ad.
No issues so far, not to say there won't be any issues
Your main issue after that is going to be dealing with double GFCI, since NEC now (as of a few years ago) requires the protection on the breaker end...and all EVSEs have their own protection already built into themselves. You'll get a lot of trips as they fight each other...but if you hardwire, this is a non issue (NEC drops the GFCI breaker requirement here) hence why hardwire is more popular now for new installs.
That said, EVSEs are an easy product to design. 50 amps or 20 amps, all they really do is let AC power run through and do some basic communication with the car. The "smart" versions just add failure points, but hopefully it can disable the "smart" features. All the AC to DC conversion happens in the actual charger inside the vehicle, unless you are talking DC fast charging, which is usually 3-phase and not worth doing at home or in most locations or for more people. If you have busy EV taxi and limo company, totally worth it.
Sign up for a Slickdeals account to remove this ad.
Your main issue after that is going to be dealing with double GFCI, since NEC now (as of a few years ago) requires the protection on the breaker end...and all EVSEs have their own protection already built into themselves. You'll get a lot of trips as they fight each other...but if you hardwire, this is a non issue (NEC drops the GFCI breaker requirement here) hence why hardwire is more popular now for new installs.
Join The Conversation